PN2210309 PRICE: $10
SG & AAE SERIES BOILERS
INSTALLATION AND SERVICE MANUAL
FOR MODELS SG-315 TO SG-495 AND AAE-480 TO AAE-3000
SEE REAR COVER FOR INDEX
Manufactured by
Allied Engineering Company
Division of E-Z-Rect Manufacturing Ltd.
Manufacturers of Gas and Electric Boilers, Stainless Steel Tanks, Heat Exchangers and Electric Boosters.
94 Riverside Drive, North Vancouver, B.C. V7H 2M6 Telephone (604) 929-1214 FAX (604) 929-5184
Branches: Calgary Edmonton Toronto
See Section 3.10 for Installer’s Checklist
See Section 4.3 for Service Checklist
This manual must only be used by a qualified
heating installer, service technician or gas supplier.

Questions and Answers

  • S
    Sherry SpearsAug 18, 2025
    What to do if I smell gas near my Super Hot AAE Boiler?
    • R
      rachel91Aug 18, 2025
      If you smell gas, consult the section 'What to do if you smell gas' on the cover of the manual. Additionally, have a certified gas fitter inspect the system for leaks and repair them. Other possible causes include: negative draft due to incorrect vent size or a blocked vent; insufficient combustion air, so check if the combustion and ventilation air openings meet installation code requirements and are not blocked.
  • J
    Jennifer GuerraAug 23, 2025
    Why is my Super Hot Boiler making a rumbling sound?
    • J
      Julie BurtonAug 23, 2025
      A rumbling or moaning sound in your Super Hot Boiler could be caused by several factors. First, the boiler may be overheated, and the safety high limit aquastat is failing to cut out; in this case, check the aquastats and adjust or replace if necessary. Improper wiring can also cause this issue; check and correct the wiring. Another potential cause is foreign matter in the heat exchanger, which can be resolved by flushing the heat exchanger. Poor circulation can also lead to these sounds; check the pump for correct flow. Lastly, air trapped in the heating system can be the culprit; in this case, purge the air from the system.
  • M
    Mrs. Heather BakerAug 25, 2025
    What causes a Super Hot AAE to continuously fire?
    • S
      Sarah ShahAug 26, 2025
      If your Super Hot Boiler fires continuously, it might be due to a gas valve failure (in the open position), so check the gas valve and replace it if necessary. Another possible cause is faulty wiring; inspect the wiring of aquastats, zone valves, and thermostats for short circuits or incorrect wiring. Lastly, a faulty aquastat, zone valve, or thermostat could be the issue; check these components and replace them if necessary.
  • J
    Jason ByrdAug 30, 2025
    Why does my Super Hot Boiler cycle on and off frequently?
    • R
      Robert LawrenceAug 30, 2025
      If your Super Hot Boiler goes on and off frequently, it might be due to poor flow in the boiler or circulator failure; check the pump for proper capacity and flow direction, and replace it if necessary. The thermostat, heat anticipator, or aquastat might be set too low, so check and adjust them. The boiler could be oversized or have insufficient radiation; check and adjust if necessary. Finally, the wrong type of thermostat or controller could be the issue; check and replace it if necessary.
  • M
    Matthew WhiteSep 1, 2025
    Why does the pilot light on my Super Hot AAE Boiler fail after ignition trial?
    • B
      Beth KirkSep 1, 2025
      If the pilot lights on your Super Hot Boiler, but there is flame failure after the trial for ignition, it could be due to incorrect pilot flame pressure; set the pilot pressure to the correct pressure. Poor connections in the wiring to the flame sensor can also cause this issue; repair the wiring. Additionally, the electrodes may be damaged, so replace them. The ignition electrodes might also be improperly adjusted; correct the adjustment of the electrodes.
  • B
    Brooke McclureSep 3, 2025
    Why won't the flame stay established on my Super Hot AAE burner?
    • M
      Matthew MartinezSep 3, 2025
      If the burner starts on your Super Hot Boiler, but the flame will not stay established, it could be due to ignition electrodes that are wet, dirty, or improperly adjusted (for electronic ignition only); check, clean, change, and/or adjust the electrodes. Another possible cause is poor connections in the wiring to the flame sensor; repair the wiring.
  • C
    christopherbutlerSep 6, 2025
    Why is my Super Hot AAE Boiler overheating but the system stays cold?
    • C
      Christopher BrownSep 6, 2025
      If your Super Hot Boiler is overheating and the system remains cold, it could be due to insufficient circulation; check the pump, clean it, and replace it if necessary. Air trapped in the piping can also cause this issue; purge the system. Improper system wiring is another potential cause; test and correct the wiring.
  • J
    Jose HolmesSep 8, 2025
    What causes my Super Hot AAE Boiler and heating system to overheat?
    • G
      Gregory BullockSep 8, 2025
      If your Super Hot Boiler and heating system overheat, it could be due to a faulty thermostat or controller; check, adjust, and replace if necessary. A faulty aquastat and/or safety high limit aquastat can also cause this issue; check, adjust, and replace if necessary. Faulty wiring is another potential cause; check the wiring for short circuits and repair.
  • L
    lori36Sep 12, 2025
    What causes pilot outages in my Super Hot AAE with a standing pilot?
    • K
      Katie RussellSep 12, 2025
      Pilot outages with a standing pilot on your Super Hot Boiler can be caused by several factors. First, the pilot flame may be improper; adjust the pilot flame. Second, the thermocouple lead to the gas valve may be loose; check and tighten the lead. Finally, the thermocouple itself may be defective; replace the thermocouple.
  • J
    Jonathan KelleySep 12, 2025
    What causes flame rollout on my Super Hot Boiler?
    • J
      Jasmine MortonSep 12, 2025
      Flame roll out on ignition or during operation of your Super Hot Boiler can be caused by carbon build up on the heat exchanger, caused by improper venting, ventilation air or low return water temperature. In this case, have a qualified service technician inspect and clean the heat exchanger and check and adjust the system. Another cause is negative draft; check the venting.

Summary

Lighting Instructions

Safety Instructions

Crucial safety information regarding gas and fire hazards, and actions to take.

Lighting Instructions for Combination Gas Valve

Step-by-step guide for lighting boilers with electronic ignition and combination gas valves.

Lighting Instructions for Non-Combination Gas Valve

Step-by-step guide for lighting boilers with electronic ignition and non-combination gas valves.

Turning Off Gas; Emergency Shut-Off

Procedure for safely turning off gas supply to the boiler or initiating an emergency shut-off.

Installation Instructions

Installation Codes and Requirements

Overview of national, provincial, and local codes that must be followed during installation.

Gas Service Piping

Instructions for proper gas piping installation, leak testing, and shut-off valve usage.

Venting Installation

Guidelines and responsibilities for proper installation of the boiler's venting system.

Startup Instructions

Boiler Startup Procedure

Step-by-step instructions for safely starting up the boiler after installation.

Gas Leak Checks

Methods for detecting and verifying the absence of gas leaks in the system.

Service & Maintenance Instructions

Troubleshooting Guide

Boiler Not Firing Issues

Common causes and solutions when the boiler fails to ignite or fire.

Gas Odor and Flame Rollout

Diagnosing and resolving gas odors and flame rollout incidents.

Pilot Flame Issues

Solutions for pilot flame problems, including no spark, incorrect adjustment, or failure to light.