MG & SG Series Boilers – Installation and Service Manual
29
Troubleshooting Guide Section 8
Problem Possible Cause Solution
No
p
ower.
Check
p
ower switches and wirin
g
.
No gas supply to boiler. Check gas source and pressure.
Gas supply pipes are not purged of air. Purge gas line.
No heat demand. Check if thermostat setting is above room
temperature and aquastat setting is above
boiler water temperature.
Flame roll-out or blocked vent safety switch
is not reset.
Push reset and diagnose cause.
Flow switch or low water cut off. Check pump capacity & flow direction.
Check for correct water levels and air locks.
Gas valve failure (closed position). Check gas valve and replace if necessary.
Thermocouple failure. Check thermocouple and replace if
necessary.
Faulty wiring. Check wiring of aquastats, zone valves, and
thermostats for loose or broken wires and
repair.
Fault
y
a
q
uastat, thermostat, or zone valve.
Check and re
p
lace if necessar
y
.
Boiler will not fire.
Pilot not lit. Relight standing pilot. (For electronic
ignition, see "Pilot flame will not light on
electronic ignition".)
Poor flow in boiler or circulator failure. Check pump for proper capacity & flow
direction. Replace if necessary.
Thermostat, heat anticipator, or aquastat
set too low.
Check and adjust.
Boiler oversized or insufficient radiation. Check and adjust if necessary.
Boiler goes on and off at
frequent intervals.
Wrong type of thermostat or controller. Check and replace if necessary.
Gas valve failure
o
en
osition
.
Check
g
as valve, re
p
lace if necessar
y
.
Faulty wiring. Check wiring of aquastats, zone valves, and
thermostats for short circuits or incorrect
wiring.
Boiler fires continuously.
Fault
y
a
q
uastat, zone valve or thermostat.
Check and re
p
lace if necessar
y
.
Boiler is overheated and safety high limit
aquastat fails to cut out.
Check aquastats and adjust or replace if
necessary.
Improper wiring. Check and correct.
Foreign matter in heat exchanger. Flush heat exchanger if necessary.
Poor circulation. Check pump for correct flow.
Rumbling and moaning
sound in boiler.
Air trapped in heating system. Purge air.
Ne
g
ative draft.
Incorrect vent size or blocked vent.
Insufficient combustion air to boiler. Check combustion and ventilation air
opening in boiler room meets installation code
requirements, and combustion air flow
openings in the boiler base and burner tray are
not blocked.
Gas odor.
Leak in gas system. See “What to do if you smell gas” on cover.
Have gas fitter test system and repair leaks.
Carbon build up on the heat exchanger,
caused by improper venting, ventilation air or
low return water temperature.
Have a qualified service technician inspect
and clean the heat exchanger and check and
adjust the system.
Flame roll out on ignition
or during operation.
Negative draft. Check venting.
Im
p
ro
p
er
p
ilot flame.
Ad
j
ust
p
ilot flame.
Thermocouple lead to gas valve is loose. Check and tighten lead.
Pilot outages with
standing pilot.
Thermocouple is defective. Replace thermocouple.