GLOBAL
We reserve the right to alter specifications. 20170744
4
3.1 Analogue Value (RO): AV R
Object
Instance
Object Name Min/Max
1 Setpoint – Preheat Temperature -9,9-9,9 [°C]
Preheat T° setpoint
2 Setpoint – Comfort Temperature 0,1-99,9 [°C]
Current Comfort T° setpoint (KWout/NV/BA+/BA-) (0=OFF)
3 Current Postheat setpoint 0,1-99,9 [°C]
Current Postheat setpoint (KWout/NV/BA+/KWext) (0=OFF)
4 Current Postcool setpoint 0,1-99,9 [°C]
Current PostCooling setpoint (BA-) (0=OFF)
5 OUT INT HYDRAULIC POSTHEAT 0-10,0 [V]
Output for the power control of the hydraulic postheater inside the unit
6 OUT EXT HYDRAULIC POSTHEAT 0-10,0 [V]
Output for the power control of the hydraulic postheater external to the unit
7 OUT EXT HYDRAULIC POSTCOOL 0-10,0 [V]
Output for the power control of the hydraulic postcooler external to the unit