5
3.3 Integer Value (RO): IV R
Object
Instance
Object Name Min/Max
1 Working Mode 0-9
Current Working mode (0=OFF 1=CA 2=LS 3=CPf 4=CPs (5=CAs) 6=TQ 9=InitPa)
2 Speed Selection I II III 0-3
Current speed (0=STOP 1=LOW/I 2=MEDIUM/II 3=HIGH/III)
3 Type of unit for ow 0-4
Current main Setpoint unit (0= m3/h 1=Pa 2=0,1V 3=torque% 4=l/s)
4 Setpoint - Supply Flow 0-99999
Current setpoint for the supply fan (unit dened in object “Type of unit for ow”)
5 Setpoint - Exhaust Flow 0-99999
Current setpoint for the exhaust fan (unit dened in object “Type of unit for ow”)
6 Exhaust/Supply ratio 5-999
% (F3F4/F1F2)
7 Actual Supply Flow 0-99999
Actual Supply Flow (unit dened in object “Type of unit for ow”)
8 Actual Exhaust Flow 0-99999
Actual Exhaust Flow (unit dened in object “Type of unit for ow”)
9 Running Hours 0-999999 [H]
Run time, working hours
10 Antifrost Status 0-2
0=OFF 1=REC ON 2=NV ON
11 Bypass Status 0-2
0=CLOSED/OFF 1=OPEN/ON 2=PARTIALLY OPEN
12 Dampers Status 0-2
0=CLOSED 1=OPENING/CLOSING 2=OPEN
13 Postventilation 0-1
Post ventilation status (0=NO 1=YES)
14 Control Mode 0-10
Control by (1=ERROR 2=FIREALARM 3=VIEWER 4=CBR 5=VIEWSCHED 6=MBSCHED
7=MB40201 8=BYPASS 9=BOOST 10=MB40204)
15 External Batteries Antifreeze Status 0-3
BA+ BA- Antifreeze status (0=OFF, 1=BA+ ON or BA+/- ON, 2=BA- ON, 3=BA+ and BA-
ON)
16 Filters Hours 0-999999 [H]
Filters alarm: hours count