5Installation
5.1Unpacking
Verifythatallorderedequipmentaredeliveredbeforestartingtheinstallation.Anydiscrepanciesfromthe
orderedequipmentmustbereportedtothesupplierofSystemairproducts.
5.2Where/howtoinstall
Theoutdoorairintakeofthebuildingshould,ifpossible,beputinthenorthernoreasternsideofthe
buildingandawayfromotherexhaustoutletslikekitchenfanoutcastsorlaundryroomoutlets.
Theunitismeantforindoorinstallation.Theelectricalcomponentsshouldnotbeexposedtolower
temperaturethan0°Corhigherthan+50°C.Theunitcanbeinstalledinacoldplaceifitisrunning
continuously.Thecontrolpanelshouldhoweverbeplacedinawarmspace.
Whenchoosingthelocationitshouldbekeptinmindthattheunitrequiresmaintenanceregularlyandthat
theinspectiondoorsshouldbeeasilyaccessible.Leavefreespaceforopeningthedoorsandfortaking
outthemaincomponents(gure7,andtablebelow).Ifthehandleandhingesoninspectiondoorsare
removedthefreespace(A)canbereducedto50mm.ThisappliesforalltheTAsizes,butrememberthat
theremustbeenoughspaceforserviceandmaintenancee.g.lterchange.
TAModelFreespace
(mm)
TA450720
TA650620
TA1100,1400,2000650
TA3000850
TA4500900
Inspectiondoorscaneasilybeeremovedsee(gure1andgure2).
TA450-4500Installationinstructions