5.6Changingfanspeed
5.6.1TA450-1400EL
Connectionblockmarked14-17areusedtosetthefanspeed,seechapter5.5.1.Defaultsettingsfor
highfanspeedareonterminalpost14(cablemarkedwith230V)andlowfanspeedonterminalpost
16(cablemarkedwith160V).
5.6.2TA2000EL
Connectionblockmarked17-24isusedtosetthefanspeed,seechapter5.5.2.
Defaultsettingsforhighfanspeedareonterminalpost17and18(cablesmarkedwith400V)andlow
fanspeedonterminalpost21and22(cablesmarkedwith240V).
Whenreconnectingtoanotherfanspeedboththecablesforhigh/lowfanspeedmustbemoved.E.g.to
reducethehighfanspeed,from400Vto320V,thecablesconnectedtothetwoterminalpostsmarked17
and18aretobemovedtothetwoterminalpostsmarked19and20.
*=Highfanspeed
**=Higfanspeed320V
5.6.3TA1400HW
Terminalpostmarked130V,160V,180Vand230Vonthetransformerisusedtosetthefanspeed.
Defaultsettingsforhighfanspeedareonterminalpost230V(thesinglecablemarkedwith230V)andlow
fanspeedonterminalpost160V(cablemarkedwith160V).
Note:
Terminalpostmarked90Visnotallowedtouse!