Topvex TR800, TR1300, TR1800, TR4000
Operation and Maintenance Instructions
Systemair Inc.
18
Main menu item Sub-menu item 1 Sub-menu item 2 Explanations
SAF: Auto
Manual set:
0.0
EAF: Auto
Manual set:
0.0
Set the heating to Auto,
Manual or Off.
Set the manual output 0-100%.
Heating
Auto
Manual set:
100.0
Set the heating to Auto,
Manual or Off.
Set the manual output 0-100%.
Exchanger
Auto
Manual set:
0.0
Set the exchanger rotor control
to Auto, Manual or Off.
Set the manual output 0-100%.
Cooling
Auto
Manual set:
0.0
Set the cooling to Auto,
Manual or Off
Set the manual output 0-100%
Note:
Needs to be activated in order
to be visible here
P1-Heating
Auto
P1-Exchanger
Auto
Set the pump control for the
heating coil to Auto,On or Off
Set the pump control for a
possible run around coil to
Auto,On or Off
P1-Cooling
Auto
Set the pump control for the
cooling coil to Auto,On or Off
Fire damper
Auto
Set the re damper to Auto,
Open or Close
Note:
Needs to be activated in order
to be visible here
Conguration of re damper
functions are made at System
level
Fresh air
damper (Outdoor
air damper)
Auto
Set the Outdoor damper to
Auto, Open or Close