Calculate minimum size of vent openings and ducts

vents use louvers or grilles to protect the opening. The louver or grill itself blocks some of the free area, so the open-
ing may need to be larger to meet the minimum free area requirements.





 
 

 Each vent opening must be no smaller than 100 square inches .
 
 Rectangular ducts must have a minimum dimension of no less than three inches .
 All screens must have mesh ¼” or larger.
 -

 
Check that air source is clean and free of chemicals
-


See graphics on next page.
Table 1

indoor spaces.

Opening Source Minimum Free Area
Direct to outdoors* 1 sq. in. per 4,000 BTU/hr (see Figure 1, 2)
 1 sq. in. per 4,000 BTU/hr (see Figure 3)
Horizontal ducts 1 sq. in. per 2,000 BTU/hr (see Figure 4)
Single Opening 1 sq. in. per 3,000 BTU/hr (see Figure 5)
Two permanent openings
to another room**
1 sq. in. per 1,000 Btu/hr (see Figure 6)
Opening: 100 in.
2
MIN.
Minimum dimension of air openings:
no less than 3 in.

an outside wall.

