1.Specification
Model
TCA‐36HRA/DVO
TCA‐48HRA/DV3O
TCA‐60HRA/DV3O
Control type
Capacity
Btu/h(W)
36000(10550)
48000(14000)
60000(17500)
Cooling
Input
W
3050
4180
5420
capacity
Current
A
15.0
8.2
9.5
EER
W/W
3.46
3.35
3.23
Capacity
Btu/h(W)
40000(11700)
53000(15530)
63000(18400)
Heating
Input
W
3224
4440
5460
capacity
Current
A
15.5
9.1
10.1
COP
W/W
3.63
3.5
3.37
Outdoor noise level(sound power levle)
dB(A)
59
60
60
Refrigerant
Type
R410A
R410A
R410A
type/Quantity
Charged volume(20m)
kg
2.70
3.80
4.1
Design pressure
MPa
4.2/1.5
4.2/1.5
4.2/1.5
Electrical Data
Power supply
220‐240V~/50Hz
380‐415V~3N /50Hz
380‐415V~3N /50Hz
Voltage Range
V
220~240
380~415
380~415
Max. Power
W
5000
7200
7600
Max. Current
A
24.3
14.5
16
Refrigerating System
Model
TNB220FFEMC‐L
MNB36FABMC
LNB42FSAMC
Type
Rotary
Rotary
Rotary
Brand
Mitsubishi
Mitsubishi
Mitsubishi
Capacity
Btu/h(W)
23679(6940)
40602(11900)
47700(13980)
Input
W
2150
3640
4270
Compressor
Rated current(RLA)
A
9
9.7
12
Locked rotor Amp(LRA)
A
/
/
/
Thermal protector
/
/
/
position
Capacitor
μF
/
/
/
Refrigerant oil
ml
720
1100
1400
Model
YDK56-6-6
YDK56-6-6
YDK56-6-6
Outdoor fan
Qty
1
2
2
Input
W
270
300
300
motor
Capacitor
μF
4
4X2
4X2
Speed(Hi/Med/Lo)
r/min
860
740
740
Outdoor coil
Number of rows
2
2
3
51/ 113