6-5 Forced Mode
In this mode the system operates (COOLING or HEATING mode – fixed settings) or is switched off by
means of the MODE button of the indoor unit control board. The operation modes can be selected
pressing the button in a cyclic way (OFF COOL HEAT OFF…). The settings are:
COOLING mode
SET POINT temperature = 25°C
FAN SPEED = HIGH
6-6 Protection Operations in Cool and Dry Mode
Freeze-up
This protection prevents ice formation on the indoor coil heat exchanger.
The protection is activated by the indoor coil temperature (ICT sensor) and only after 6 minutes
of compressor operation.
This protection acts in 2 levels:
LEVEL 1
FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: ON
DRAIN PUMP: operates according to paragraph 6-9
LEVEL 2
FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: OFF for at least 6 minutes and until ICT 8°C
DRAIN PUMP: always ON ( stops when exiting the protection)
The system exit this protection routine when ICT temperature rises above 8°C.