1. SPECIFICATIONS
1-1 Unit Specifications
CWX3B5XAB
Power source
Performance
Input kW
Running Amps A
Total cooling capacity (1) High/Med./Low
kW
Sensible cooling capacity (1) High/Med./Low
kW
Heating capacity (2) High/Med./Low
kW
Air circulation High/Med./Low m³/h
Features
Controls/Temperature controls
Control unit
Timer
Fan speed
Airflow direction
Water FLOW in cooling
High/Med./Low
l/h
Pressure drop on water in cooling (1)
High/Med./Low
kPa
Pressure drop on water in heating (2) High kPa
Air Filter
Power noise level High/Med./Low dB-A
Water tubing connections
Air clean filter
3-Way valve + By-pass (1/2 gas male, KVS 1,6, 230 NC)
Dimensions & Wei
ht
Dimensions Unit Height mm
Width mm
Depth mm
Ceiling panel Height mm
Width mm
Depth mm
Package dimensions Unit Height mm
Width mm
Depth mm
Volume
m
3
Ceiling panel Height mm
Width mm
Depth mm
Volume
m
3
Weight Unit Net kg
Shipping kg
Ceiling panel Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
(1)
Air inlet 27°C (D.B.) / 19°C (W.B.); Water inlet 7°C; Water outlet 12°C
(2)
Air inlet 20°C; Water inlet 50°C (same water capacity as in conditions (1))
OPERATION LIMITS
Min. water inlet temperature 4°C Min. air recirculation temperature 5°C
Max. water inlet temperature 60°C Max. air recirculation temperature 32°C
Max. operating pressure of hydraulic circuit 16 bar
22,7
2,50
4,70
273
575
575
64
730
730
380
744
650
Washable, polypropylene, class HB (UL94)
0,18
Optional
46/43/40
Optional
1/2" gas female
110
800
800
0,07
18,2
0,052
0,24
Auto (Remote control)
Microprocessor/ I.C. thermostat
ON/OFF 24 hours
Wireless remote control unit
447/395/360
22,0/18,0/15,0
18
230 V - 50 Hz
2,31/2,09/1,91
3 and Auto
2,6/2,35/2,15
520/460/400
3,49/3,11/2,83
3