1. Specifications
1
2
3
4
5
I-107
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit :CAV250R5TAA Outdoor Unit :GRV250R5TAA
GRV250L5TAA
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions:Indoor Air Temperature35°C DB / 25°C WB
Outdoor Air Temperature 43°C DB
Heating:
Rating Conditions : Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions:Indoor Air Temperature27°C DB
Outdoor Air Temperature21°C DB / 15.5°C WB
Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz
Rating conditions
A 0.6 / 0.63 0.62 / 0.65 12.1 / 12.3 13.32 / 13.58
kW 130 / 150 0.13 / 0.15 2.55 / 2.7 2.81 / 3.0
Full load conditions
A 0.6 / 0.63 0.62 / 0.65 13.44 / 13.48 14.66 / 14.76
kW 130 / 150 0.13 / 0.15 2.8 / 2.88 3.06 / 3.18
Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75
Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 1 phase / 50 Hz
Rating conditions
A 0.37 / 0.42 0.62 / 0.65 13.7 / 13.5 14.69 / 14.57
kW 80 / 100 0.13 / 0.15 2.86 / 2.96 3.07 / 3.21
Full load conditions
A 0.37 / 0.42 0.62 / 0.65 15.6 / 15.2 16.59 / 16.27
kW 80 / 100 0.13 / 0.15 3.25 / 3.29 3.46 / 3.54
Starting amperes A 1 / 1 1 / 1 67 / 73 69 / 75