1. Specifications
1
12
3
4
5
I-108
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : CAV250R5TAA Outdoor Unit :GRV250R7TAA
GRV250L7TAA
Cooling:
Rating Conditions : Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions:Indoor Air Temperature35°C DB / 25°C WB
Outdoor Air Temperature43°C DB
Heating:
Rating Conditions:Indoor Air Temperature20°C DB
Outdoor Air Temperature7°C DB / 6°C WB
Full Load Conditions:Indoor Air Temperature27°C DB
Outdoor Air Temperature 21°C DB / 15.5°C WB
● Cooling
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 0.6 / 0.63 0.62 / 0.65 4.45 / 4.35 4.82 / 4.73
kW 130 / 150 0.13 / 0.15 2.5 / 2.52 2.76 / 2.82
Full load conditions
A 0.6 / 0.63 0.62 / 0.65 5.3 / 5.32 5.67 / 5.69
kW 130 / 150 0.13 / 0.15 2.98 / 3.02 3.24 / 3.32
Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30
● Heating (Heat pump only)
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 220 - 240 V / 1 phase / 50 Hz 380 - 415 V / 3 phase / 50 Hz
Rating conditions
A 0.37 / 0.42 0.62 / 0.65 5 / 4.8 5.31 / 5.12
kW 80 / 100 0.13 / 0.15 2.79 / 2.81 3 / 3.06
Full load conditions
A 0.37 / 0.42 0.62 / 0.65 5.1 / 4.9 5.41 / 5.22
kW 80 / 100 0.13 / 0.15 2.87 / 2.89 3.08 / 3.14
Starting amperes A 1 / 1 1 / 1 25 / 28 27 / 30