6. ELECTRICAL DATA
6-1 Electrical characteristics
OUTDOOR UNIT: GRF98L5TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,12 0,28 3,00 3,40
Power input Kw 0,027 0,063 0,680 0,770
Full load conditions Running Amps. A 0,12 0,28 3,60 4,00
Power input Kw 0,027 0,063 0,790 0,880
NOTE: Data referred to indoor unit MRAF98C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF128L5TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,13 0,28 4,29 4,70
Power input Kw 0,031 0,063 0,956 1,050
Full load conditions Running Amps. A 0,13 0,28 5,09 5,50
Power input Kw 0,031 0,063 1,156 1,250
NOTE: Data referred to indoor unit MRAF128C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF188L5TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,37 0,41 6,32 7,10
Power input Kw 0,070 0,087 1,443 1,600
Full load conditions Running Amps. A 0,37 0,41 7,72 8,50
Power input Kw 0,070 0,087 1,793 1,950
NOTE: Data referred to indoor unit MPAF188C5T model.
For other indoor unit models there could be some differences.
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz