OUTDOOR UNIT: GRF188L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,37 0,41 2,62 3,40
Power input Kw 0,070 0,087 1,493 1,650
Full load conditions Running Amps. A 0,37 0,41 3,32 4,10
Power input Kw 0,070 0,087 1,943 2,100
NOTE: Data referred to indoor unit MPAF188C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF228L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,40 0,67 3,13 4,20
Power input Kw 0,086 0,144 1,850 2,080
Full load conditions Running Amps. A 0,40 0,67 3,93 5,00
Power input Kw 0,086 0,144 2,370 2,600
NOTE: Data referred to indoor unit MPAF228C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF258L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,77 0,67 3,66 5,10
Power input Kw 0,175 0,144 2,261 2,580
Full load conditions Running Amps. A 0,77 0,67 4,76 6,20
Power input Kw 0,175 0,144 3,081 3,400
NOTE: Data referred to indoor unit CAF258C5
T
model.
For other indoor unit models there could be some differences.
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz