OUTDOOR UNIT: GRF368L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,92 1,34 4,34 6,60
Power input Kw 0,210 0,29 2,802 3,300
Full load conditions Running Amps. A 0,92 1,34 5,14 7,40
Power input Kw 0,210 0,29 3,402 3,900
NOTE: Data referred to indoor unit CAF368C5
T
model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF488L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor
performance at
Rating conditions Running Amps. A 0,92 1,34 7,44 9,70
Power input Kw 0,210 0,29 4,502 5,000
Full load conditions Running Amps. A 0,92 1,34 9,34 11,60
Power input Kw 0,210 0,29 5,902 6,400
NOTE: Data referred to indoor unit CAF488C5
T
model.
For other indoor unit models there could be some differences.
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz