1 - 27
Capacity [minimum~maximum] kW
BTU/h
Air circulation (Hi/Me/Lo) m3/h
Moisture removal (High) Liters/h
External static pressure (High) Pa(mmAq)
Voltage rating V
Available voltage range V
Running amperes* A
MaxRunning amperes** A
Power input kW
C.O.P W/W
Max. Starting amperes A
Controls/Thermostat control
Timer
Fan speeds Indoor/Outdoor
Airflow direction (Indoor)
Air filter
Remote controller (Option)
Refrigerant control
Drain pump (Drain connection)
Compressor
Operation sound Indoor - Hi/Me/Lo dB - A
Outdoor - Hi dB - A
Color (Approximate value) Indoor
Outdoor
REFRIGERANT TUBING
Limit of tubing length m (ft.)
Limit of tubing length at shipment m (ft.)
Limit of elevation difference m (ft.)
between the two units
Refrigerant tube Narrow tube mm (in.)
outer diameter Wide tube mm (in.)
Refrigerant amount at shipment kg
DIMENSIONS & WEIGHT
Unit dimensions Height mm (in.)
Width mm (in.)
Depth mm (in.)
Package dimensions Height mm (in.)
Width mm (in.)
Depth mm (in.)
Net weight kg (lb.)
Shipping weight kg (lb.)
Shipping volume
m
3
(cu. Ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
198 - 264 198 - 264
17.9 17.1
MODEL No. Indoor Unit DSAFP365R
Outdoor Unit GRFP365R
POWER SOURCE 220 - 230 - 240 V/1 phase/50/60 Hz
PERFORMANCE Cooling Heating
10.0 [2.2~11.2] 11.2 [2.2~12.5]
34,000 [7,500~38,000] 38,000 [7,500~42,500]
1,800/1,560/1,260
4.2
79 (8.1) : at shipment, 122 (12.4) : using the booster cable
ELECTRICAL RATINGS
220 230 240 220 230 240
16.4 16.6 16.0 15.4
3.53 3.55 3.56 3.28
3.39 3.38
3.30 3.31
2.81 3.41
FEATURES
2.83 2.82
Microprocessor/I.C.thermostat
ON/OFF 72-hours
3 and Automatic control/Variable
Field supply
Wired : REM HW Wireless : REM HL
Max.head 50 cm above drain connection (25A , OD32mm)
Rotary(SANYO)
38/33/31, (42/38/33 : using the booster cable)
51/52
Munsell 1Y 8.5/0.5
50 (164)
5~30 (16~98)
Outdoor unit is higher than indoor unit : 30 (98)
Outdoor unit is lower than indoor unit : 15 (49)
9.52 (3/8)
15.88 (5/8)
R410A - 2.8
Indoor unit Outdoor unit
340 (13-3 /8)
358 (14-3/32) 888 (34-31/32)
310 (12-7/32) 780 (30-23/32)
1,480 (58-9/32) 940 (37)
65 (143)
52 (115) 73 (161)
47 (104)
0.468 (16.5) 0.369 (13.0)
1,671 (65-25/32) 1015 (39-31/32)
783 (30-26/32) 409 (16-3/32)
630 (24-26/32)
1-1. Unit Specifications
Concealed-Duct Type DSAFP365R / GRFP365R
04-163 Sanyo-1_p30-61 7/28/04 5:46 PM Page 59