10
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POWK188E
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RCS8PS3E
Type Cross-flow
Q´ty ... Dia. and length mm 1 ... ø88 / L746
Fan motor model ... Q´ty UF2– 31A5PAS ... 1
No. of poles ... rpm (High) 2 ... 1,305
Nominal output W 30
Coil resistance (Ambient temp. 20°C) WHT – BRN : 130.4
WHT – PNK : 169.8
– :
– :
– :
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 2.0
VAC 440
Type Stepping motor
Model MP24GA2
Rating DC 12 V
Coil resistance (Ambient temp. 20°C) Each terminals (1–2, 1–3, 1–4, 1–5) 400 : ± 7%
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.3
Face area m2 0.250
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit MCAV180C5VAA

Table of Contents