5-2. Cooling capacity
INDOOR UNIT: MCAV180C5VAA
OUTDOOR UNIT: GRV180C7TAA
400V 50 Hz
RATING CAPACITY 5 kW
AIR FLOW RATE 760 m³/h
EVAPORATOR CONDENSER
ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 4,83 4,69 4,47 4,19 3,87
CM 1,73 1,84 1,98 2,18 2,37
21 SHC 3,31 3,25 3,14 3,00 2,85
23 SHC 3,76 3,68 3,57 3,44 3,28
15 25 SHC 4,19 4,10 3,99 3,86 3,70
27 SHC 4,63 4,53 4,42 4,19 3,87
29 SHC 4,83 4,69 4,47 4,19 3,87
31 SHC 4,83 4,69 4,47 4,19 3,87
TC 5,23 5,03 4,79 4,50 4,15
CM 1,77 1,90 2,04 2,24 2,43
21 SHC 2,90 2,82 2,71 2,57 2,41
23 SHC 3,33 3,24 3,13 2,99 2,84
17 25 SHC 3,78 3,67 3,56 3,43 3,26
27 SHC 4,21 4,09 3,98 3,85 3,69
29 SHC 4,66 4,52 4,41 4,28 4,11
31 SHC 5,09 4,94 4,79 4,50 4,15
TC 5,54 5,36 5,10 4,79 4,41
CM 1,86 1,96 2,10 2,30 2,50
21 SHC 2,43 2,35 2,24 2,11 1,95
23 SHC 2,85 2,78 2,67 2,54 2,38
19 25 SHC 3,27 3,20 3,09 2,97 2,81
27 SHC 3,69 3,64 3,53 3,39 3,24
29 SHC 4,10 4,06 3,95 3,83 3,66
31 SHC 4,53 4,49 4,38 4,25 4,09
TC 5,88 5,68 5,41 5,08 4,68
CM 1,90 2,01 2,16 2,37 2,57
23 SHC 2,40 2,32 2,21 2,07 1,92
21 25 SHC 2,81 2,74 2,64 2,51 2,35
27 SHC 3,23 3,17 3,06 2,94 2,77
29 SHC 3,64 3,59 3,49 3,36 3,20
31 SHC 4,07 4,02 3,91 3,79 3,64
TC 6,28 6,01 5,68 5,31 4,94
CM 1,93 2,06 2,22 2,42 2,64
23 25 SHC 2,35 2,25 2,13 2,00 1,86
27 SHC 2,75 2,67 2,55 2,42 2,28
29 SHC 3,17 3,10 2,98 2,85 2,72
31 SHC 3,62 3,54 3,40 3,27 3,15
TC: TOTAL COOLING CAPACITY kW
SHC: SENSIBLE HEAT CAPACITY kW
CM: COMPRESSOR INPUT kW
RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B.
INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
31