DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW-C181BL (Only CLR model)
Control circuit fuse 250V – 5A (Only CLR model)
Type Rotary (Hermetic)
Compressor model C-2RN173H8W 80807088
Source 380 – 400 V – 3N
~
50 Hz
Nominal output W 1,700
Compressor oil ... Amount cc FV68S ... 800
Coil resistance (Ambient temp. 25°C) C – R : 6.369
C – S : 6.073
R – S : 6.217
Type Internal protector External protector
Safety
Overload relay HE-10TB TH-5A
devices
Operating temp.
Open °C Automatic opening
Close °C Automatic reclosing
Operating amp.(Ambient temp. 25°C) 5A
Run capacitor
µF
VAC
Crank case heater 240V 30W
Type Propeller
Q´ty ... Dia. mm 1 ... ø400
Fan motor reference model ... Q'ty SMEN 19 TFB6047 ... 1
Source 220 – 230 V
~
50 Hz
No. of poles ... rpm (220 V, High) 6 ... 910
Nominal output W 43
Coil resistance (Ambient temp. 20°C) WHT – BRN : 83.4
WHT – PNK : 218.7
Safety
Type Internal type
devices
Operating temp.
Open °C 130 ± 5
Close Automatic reclosing
Run capacitor
µF 2.0
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 2
Fin pitch mm 1.8
Face area m
2
0.508
External Finish Acrylic baked-on enamel finish
Controller
PCB
Heat
Exch. Coil
Compressor
Fan & Fan Motor
14
Outdoor Unit GRV180C7TAA / GRV180L7TAA
2-2-2. Outdoor Unit

Table of Contents