Rating Conditions: Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions: Indoor Air Temperature 32°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50Hz
Rating Conditions
Running Amps. A 0.28 0.40 3.15 3.6
Power Input kW 0.072 0.086 1.98 2.0
Full Load Conditions
Running Amps. A 0.33 0.40 3.37 4.1
Power Input kW 0.071 0.082 2.247 2.4
400 V – 3N ~ 50Hz
Rating Conditions: Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions: Indoor Air Temperature 32°C DB / 23°C WB
Outdoor Air Temperature 43°C DB
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 V ~ 50Hz
Rating Conditions
Running Amps. A 0.28 0.44 4.02 4.8
Power Input kW 0.066 0.113 2.57 2.80
Full Load Conditions
Running Amps. A 0.40 0.55 4.85 5.6
Power Input kW 0.083 0.120 3.18 3.40
400 V – 3N ~ 50Hz
Indoor Unit
Outdoor Unit
KPAV220C5VAA
GRV220C7TAA
39
KPAV180C5VAA