8-2.Air conditioner does not operate.
8-2-1.Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 2Mor less, insulation is defective (“NO”).
NO
Measure insulation
resistance of electrical
parts in outdoor unit.
NO
Set circuit breaker to OFF.
*
Measure insulation
resistance of electrical
parts in indoor unit.
1
Remove inter-unit wires from
terminal plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2
Remove inter-unit wires from
terminal plate in indoor unit.
Then, pull the power plug out of
the wall outlet
Measure insulation resistance
of indoor unit.
Insulation of
outdoor unit
is defective.
Insulation of
indoor unit
is defective.
WARNING
LL
NN
1
2
3
4
1
2
3
4
Outdoor
unit
1
Indoor
unit
22
Inter–unit
wiring
Circuit
breaker
Ground
Ground
Power plug
(Local supply)
Wall outlet
(receptacle)
Single phase
220–240V ~ 50Hz
43