5-4 Auto Mode Operation (only monosplit)
In Auto Mode, the unit switches automatically between the Auto Cooling and Auto Heating in order t
o
maintain the room temperature (RAT) at the prescribed set point (SPT).
The switching between the two modes is according to the above graph and following tabl
e
If -3°C Dt -1°C and the compressor is off for more than 1 hour
If Dt -3°C and compressor is off for more than 3 minutes
If 1°C Dt 3°C and the compressor is off for more than 1 hour
If Dt 3°C and compressor is off for more than 3 minutes
Dt = RAT - SPT
Refer to the sections 5.1 COOLING MODE and 5.2 HEATING MODE for system operation details.
COOLING ---> HEATING
HEATING ---> COOLING