5-5 Dry Mode Operation
Dry operation remove moisture from indoor air running, in cooling mode, at a low level without reducin
g
the ambient temperature. This is done cycling ON and OFF indoor and outdoor units according to below.
ROOM DRY LEVEL
TEMP
SPT+2°C LEVEL 0 Operation according to COOLING mode
CM on at constant speed
< SPT+2°C LEVEL 1 FMO on at constant speed
SPT-1°C FMI switches between L and LL every 30 second
s
RV off
CM switches 9 minutes off and 3 minutes on
< SPT-1°C LEVEL 2 FMO switches 9 minutes off and 3 minutes ON
15°C FMI switches between L and LL every 30 second
s
RV off
CM off
< 15°C DRY OFF ZONE FMO off
FMI off
RV off
SPT = Set Point Temperature
5-6 Fan Mode Operation
With this mode, the indoor fan is turned on while CM, FMO and RV stay off all the time. The user can
select between 3 speeds: HIGH, MEDIUM and LOW.
5-7 Auto Fan speed
With this option selected, the indoor fan speed changes automatically according to the compressor
speed as shown in the following graph
s
to prevent the supply of cool air, the FMI speed is setted as shown only if the indoor coil temperature ICT 32°C
( see COLD DRAFT PREVENTION feature for details )