EasyManua.ls Logo

Technibel PHRT 9 - Page 6

Technibel PHRT 9
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GB
6
4.2 - HYDRAULIC CONNECTION
Connect the water pipes to the corresponding connections. See Ø and position on page 4.
Install the hydraulic filter (supplied) on the water intake. Connect it using 2 isolation valves for cleaning purposes.
Install a shut-off valve if a fill/drainage connection is used.
NOTE:
"Water connection hose" accessories may be used (refer to the accessories paragraph).
4.3 - ELECTRICAL CONNECTION
4.3.1 - GENERAL:
The acceptable voltage variation is: ± 10% during operation.
The electrical connection conduits must be fixed.
Use the cable clamps at the rear of the unit and route the wires under the electric panel, at the level of the terminal strips.
Class 1 unit.
The electrical installation must comply with the standards and regulations applicable where the unit is being installed (in
particular NF C 15-100 IEC 364).
4.3.2 - POWER SUPPLY
The power supply must come from an isolation and electric protection device (not supplied) in accordance with existing
regulations.
The installation must be protected by a double-pole circuit-breaker (not included).
Note:
The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or TN.S regime
(to neutral) as per NF C 15-100.
POWER SUPPLY CABLE
Section 230V/1/50Hz : 3 G 4 mm
2
for PHRT 9 and PHRT 12.
Section 400V/3N/50Hz : 5 G 2.5 mm
2
for PHRT 12, 16 and 5 G 4 mm
2
for PHRT 18.
The sections are given as an indication only. They have to be verified and adapted, if necessary, according to the
installation conditions and the standards in force.
Make the electrical connections to the terminal board as per the electrical diagrams.
CURRENT
CAUTION:
In the case of a three-phase power supply, prior to commissioning the unit, make sure that the phase rotation
order is correct. If the rotation order is not respected:
- PHRT 12,16: the phase-sequence controller restricts the unit from operating.
- PHRT 18: the compressor will turn backwards (and make an abnormal noise).
To fix this, simply invert the 2 phases.
4.3.3 - CONTROL BY EXTERNAL CONTACTS
The machine is factory-wired for heating mode operation. The unit can be controlled remotely by connecting two good-
quality external potential-free contacts (not supplied) :
-1 for the remote On/Stand-by signal (contact closed = operation authorized, contact open = stand-by),
-1 for change-over of the operating mode (contact closed = heating mode, contact open = cooling mode).
The On/Stand-by signal is connected to terminals 1 and 2 of the PCB located in the switch box (remove the existing
bridge - see diagram).
The mode change-over signal is connected to terminals 3 and 4 of the
PCB (remove the existing bridge - see diagram).
The wiring of these contacts must not be routed near power cables in
order to avoid electromagnetic disturbances.
Use shielded cable with twisted pairs (shielding grounded on
generator side).
Max. connection cable length: 100 m.
•Minimum wire size: 0.5 mm
2
.
CAUTION:
Mode changes (heating/cooling) are to be performed with the
unit shutdown.
PHRT 9 PHRT 12 PHRT 12 PHRT 16 PHRT 18
230/1/50 230/1/50 400/3N/50 400/3N/50 400/3N/50
Nominal current A 15 17 7.5 10.9 13
Max. current A 18 20 10 13 17
Starting current A 86 89 56 63 101
Start-up current with
single-phase start-up kit
A 42 43 _ _ _
1
2
4
3
PHRT
On/Stand-by
Operating
mode
() Jumper to be removed
()
()

Other manuals for Technibel PHRT 9

Related product manuals