12
R.D. 28 Reyrieux BP 131 01601 Trévoux CEDEX France
Phone 33 4 74 00 92 92 - Fax 33 4 74 00 42 00
R.C.S. Bourg-en-Bresse B 759 200 728
11 - INSTALLATION INFORMATION
See details in the installation manual.
11.1 - INSTALLATION
Protection index of the unit:
- IP 44 : for the electrical equipment,
(IPXXB : for the mechanical hazards).
Before installation, verify the following points:
- the unit must be installed outside in an appropriate location and in compliance with environmental requirements (sound
level, integration, etc...),
- the water chiller’s installation location must be perfectly level and strong enough to support the weight of the unit and must
have adequate inundation protection,
- sufficient space around the unit should be provided in order to facilitate servicing and maintenance operations,
- air suction to the coil and fan discharge must not be obstructed,
- install the unit above the region’s average snowfall level.
- vibrations and noise must not be transmitted to adjacent buildings,
- install the machine on anti-vibration pads and fit hoses on piping elements, as required,
- if necessary, consult an acoustics specialist concerning the unit’s optimum location,
-4 holes Ø 22.5 enable to place hoisting hooks and lift the unit.
11.2 - ELECTRICAL CONNECTIONS
All required information is indicated on the electrical diagram provided with the unit and in the installation manual.
Connections are to be made in compliance with the standard code of practice and as per the standards in force at the site
of installation.
11.3 - HYDRAULIC CONNECTIONS
The hydraulic connections are to be made in compliance with
the standard code of practice.
IMPERATIVE: Install the filter supplied on the water inlet of
the unit.
11.4 - STARTING - MAINTENANCE
Refer to the installation guide and the maintenance manual.
IMPORTANT:
- Without anti-freeze resistance option
If a freeze risk is present, one must:
- either drain the installation,
- or inject glycol into the system.
- With the anti-freeze resistance option
The electrical power supply must be separate from
the generator power supply (if power the generator
is cut, the unit would no longer be protected from
freezing). External installation pipework must be
protected.
10 - SOUND LEVELS
Nominal operating conditions:
- Ambient temperature: 35°C.
• Sound-pressure level:
- Unit installed outdoors (free field) on a reflective
surface.
- Mesasurement carried out at a distance of 10 m.
Distance
in metres
dB to be
deducted from
the sound
power level
40
35
30
25
10 15 20 25 30
PMHRV
2044
2050
2064
2072
Sound-pressure
level (dBA)
50
48
52
57
Power level
(dBA)
78
76
80
85
Due to our policy of continuous development, our products are liable to
modification without notice.