EasyManua.ls Logo

Technibel PMHRV Series - Factory Fitted Options

Default Icon
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
2.3 - ACCESSORIES
2.3.1 - ANTI-VIBRATION KIT
Kit includes:
-1 set of 4 anti-vibration plates, thickness 25 mm - code K 60 L 035 Z.
-1 set of 2 flexible hoses: length 1.5 m, Ø 1" 1/2 - code K 60 L 034 Z.
2.3.2 - REMOTE CONTROL UNIT (supplied with the unit)
Ensures remote On/Off control and Heating/Cooling selection (link not provided; max. length = 100 m).
3 - FACTORY FITTED OPTIONS
3.1 - HP and LP PRESSURE GAUGES
Code K 60 X 002 M for PMHRV 2044, 2050 and 2064,
Code K 60 X 004 M for PMHRV 2072.
These elements, mounted on the vertical members of the unit's front face, display the high and low pressure values for each
refrigeration circuit.
3.2 - OPTIONAL BACK-UP PUMP
Code K 60 L 064 M for PMHRV 2044 to 2072.
The switchover of the electrical supply onto the 2
nd
pump is performed manually by a switch box placed near the pumps.
3.3 - ANTI-FREEZE RESISTANCE
Code K 60 C 010 M.
Immersion heater mounted on the tank of the hydraulic module.
Power: 800 W, single-phase 230 VAC.
With limiting thermostat.
The power supply and heating element control are to be done separately at the time of installation (not supplied).
NOTE: The anti-freeze heating element cannot be installed with the supplementary heating option (paragraph 3.6).
3.4 - PROPORTIONAL "HEAD PRESSURE" CONTROL KIT
Code K 60 G 031 M for PMHRV 2044 to 2072.
This function is operational only in "cooling" mode.
Required for units operating in environments in which outside air temperature is below +14° C.
Varies fan speed according to the condensation pressure.
Factory-set for optimal operation. For all other settings, consult us.
3.5 - REMOTE "µCHILLER" DISPLAY KEYBOARD
Code K 60 D 037 M.
Enables transfer of display keyboard functions up to 150 m.
See the manual which accompanies this accessory.
IMPORTANT:
With this accessory, the µCHILLER control is factory-configured for startup using the specific cooling or heating
keys on the display keypad.
In this case, the digital On/Off and Remote Heating/Cooling Inversion inputs are Inactive.
By special factory-set parameters (specify when ordering), these digital inputs may remain active. In this case, the
cooling and heating keys on the display keypad are inactive.
IMPORTANT:
•In the case of PMHRV units with the electric heating option, the cooling , and heating keys on the display
keypad are inactive. The On/Off and Heating/Cooling inversion commands are thus made by the remote selector supplied
with the unit or with the control box (optional item).