EasyManua.ls Logo

Technibel PMHRV Series - Page 4

Default Icon
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
2.2 - COMPOSITION OF UNIT
i
f
e
b
d
c
4
6
1
g
a
j
h
2
8
5
3
7
9
9
Supply
to installation
Return from
installation
PMHRV
CONTROL 7
Microprocessor µCHILLER control module, including:
- Chilled water temperature control.
- Control of operating parameters.
- Anti-short cycle system.
- Hour counter for each compressor.
- Automatic balancing of compressor operating time
(dual compressors).
- Air exchanger defrosting.
- Anti-freeze security (water exchangers).
- Digital display of:
. water temperature,
. set-point,
. alarm code (HP, LP, water output, thermal
protective devices, probes, anti-freeze…).
- Possibility of remote alarm signaling by a voltage-free
change-over contact and operating conditions via
remote µCHILLER display keypad (optional).
- Remote On/Off control via µCHILLER display keypad
(optional) or by voltage-free closing contact (remote
control box supplied with the unit).
- Circulation pump control.
The thermostat controls fan rotation speed according to
the ambient temperature.
For special applications, consult us.
CHASSIS - BODYWORK 8
Galvanised sheet metal with light grey oven-baked
polyester powder paint.
BUILT-IN HYDRAULIC MODULE 9
a -1 polyurethane insulated sheetmetal buffer tank.
b -1 pump with insulated control valve - 2 shut-off valves.
c -1 filling valve Ø 1/2" female.
d -1 pressure gauge, 0-4 bar.
e -1 lack of water safety pressure switch.
f -1 safety valve.
g -1 air relief valve.
h -1 drainage valve.
i -1 expansion tank.
j - Placements for electric heating elements.
COMPRESSOR 1
Hermetic SCROLL compressor with sound-proofing
cover.
Installed on rubber anti-vibration pads.
Internal thermal protection of the motor winding.
Crankcase heater.
CONDENSER 2
Coil, consisting of copper pipes and crimped aluminium
fins.
Protective grille.
Condensation pressure probe with the proportional "All-
season" control.
Probe for defrosting.
FAN 3
Direct driven axial fan.
2-speed motor, Y/ switching, 400V/3Ph/50Hz.
Rotation speed 700 - 550 rpm.
Insulation classification F.
Internal thermal protection.
Protection class IP55.
Proportional "All-season" control, available as option.
EVAPORATOR 4
Plate-type stainless steel (AISI 316L) water treatment
section with freezing protection.
Antifrost electric heating resistor.
Water circulation controlled by differential pressure switch.
Water inlet temperature probes (for control).
Temperature probe for antifrost protection.
REFRIGERANT CIRCUIT 5
•R 407 C refrigerant.
Thermostatic expansion valve.
Drier filter.
•Automatic reset high pressure and low pressure
switches.
Copper tubing.
Liquid receiver.
SWITCH BOX 6
Accessible via hinge-mounted door.
Main switch.
Phase-sequence tester.
Power and control circuitry protected by magnetothermal
circuit breakers.
Complies with standard EN 60 204-1.
Short circuit current 10 kA, as per IEC 947-2.