EasyManua.ls Logo

TECHTOP TD20 Series - Page 37

TECHTOP TD20 Series
131 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TD20 Series VFD Function Parameters
-35-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P01.23
Start delay
time
The function determines the brake release after the
running command is given, and the VFD is in a stand-by
state and wait for the delay time set by P01.23
Setting range: 0.060.0s
0.0s
P01.24
Delay of the
stopping
speed
Setting range: 0.0100.0s
0.0s
P01.25
0Hz output
Select the 0Hz output of the VFD.
0: Output without voltage
1: Output with voltage
2: Output at the DC braking current
0
P02 Group Motor 1
P02.01
Rated power
of
asynchronous
motor
0.13000.0kW
Note: The value entered in this parameter must be in
kW.
Power (kW)
Horsepower (HP)
0.4
0.5
0.75
1
1.5
2
2.2
3
Depend
on
model
P02.02
Rated
frequency of
asynchronous
motor
0.01HzP00.03
60.00Hz
P02.03
Rated speed
of
asynchronous
motor
136000rpm
Depend
on
model
P02.04
Rated voltage
of
asynchronous
motor
01200V
Depend
on
model
P02.05
Rated current
of
asynchronous
motor
0.86000.0A
Depend
on
model

Related product manuals