5.8 General test parameters
The general parameters apply to all types of testing.
5.8.1 Management parameters
phases; range 0: 25 s; 0=not used.
PSIN
Consent input upon Start: the test starts only if the selected input is active and ends
if the signal is deactivated.
: not used;
: manual button on the front panel;
: double safety START inputs;
, range 1: 16.
Auxiliary output: PLC output activated with the Start command, according to the
mode programmed in the parameter: PSOUT: mode .
NO: not used;
, range 1: 16.
Auxiliary output: at the Start command, the output programmed in the parameter
PSOUT: output can be activated as desired with the following modes:
: auxiliary output not active.
: pre-adjustment with external valve, to keep the connection pipe to the
component being tested under pressure.
: the output is activated at the start and is maintained until the end
of the test.
: the output is activated at the start with the PSDEL delay and is
maintained until the end of the test.
: the output is active at the beginning of the PSDEL delay and is
deactivated at the end of the PSDEL delay.
T0: the output is active at the beginning of time T0 and is deactivated at the end of T0.
T1: the output is active at the beginning of time T1 and is deactivated at the end of T1.
T2: the output is active at the beginning of time T2 and is deactivated at the end of T2
T3: the output is active at the beginning of time T3 and is deactivated at the end of T3
: the output is always active when the test program is selected for testing
(active program).