11
TANK
CHILLER LINE
5.2.1 Information on the display
On: unit in cooling mode (Ref. A9 Fig. 12).
On: unit in heating mode (Rif. B1 Fig. 12).
Flashing light: unit ready for cooling (Rif. A9 Fig. 12).
Flashing light: unit ready for heating (Rif. B1 Fig. 12).
On: alarm condition (Rif. A1 Fig. 12).
5.2.2 Thermostat settings
Refer to fi gure 12 for buttons detection.
1) To change the temperature of the water:
a. Push the button SET for 3 seconds (Rif. A8), display shows the current value setting and the unit of
measure icon (C or F ref C3) starts to blinking.
b. Modify the parameters using the arrows
and (Rif. C2 and A7) (5 ÷ 35°C / 41 ÷ 95°F).
c. Push the button SET (Rif. A8) to confi rm the values.
2) To adjust other parameters: hysteresis function (Hy), probe calibration (Ot), exclude the heater (O1):
d. Access to the programming menu by pressing the SET+ button for 3 seconds (Ref. A7 and A8). The
icon unit selected starts blinking (C or F ref C3) and appears Hy.
e.
Scroll through the parameters using the arrows and (Ref.C2 and A7) until the desired parameter.
f. Press the SET button (ref A8), the current set value is displayed.
g. Change the value using the arrows and (Rif. C2 and A7).
h. Press the SET button (Ref. A8) to confi rm the setting and move to the next parameter.
i. Press SET + (Ref. A8 and C2) to exit programming mode.
NOTE: If you do not press any buttons for 30 seconds, all settings are saved and the device is
ready for operation.
Parameter Preset value Description Regulation range
Hy 1°C
This parameter sets the hysteresis, that is the
diff erential of the unit.
0,5 ÷ 10°C
1 ÷ 45°F
Ot 0°C
This parameter adjusts the probe calibration: it
allows to compensate for the diff erence in tem-
perature reading on the display with respect to
the actual water temperature.
-12 ÷ 12°C
-20 ÷ 20°F
o1 On
Activation / deactivation of the heating function:
In this model, the resistance is absent.
Just set it to “OFF”.
On - OFF
rL xx.x
Firmware version of thermostat.
Read-only parameter.
-
Tab. 5-2
5.3 TRANSPORTATION AND STORAGE
The chiller must be handled carefully in a vertical position.
It is recommended to place it on a fl at surface.
5.4 DEMOLITION AND DISPOSAL
The crossed-out wheelie bin label that can be found on your products, indicates that the product may not be
treated as household waste. By ensuring that this product is disposed of correctly, you will help preventing poten-
tial negative consequences for the environment and human health, which could otherwise be caused by inappro-
priate waste handling of these products. For more detailed information about recycling of this product, please
contact your local city offi ce, your household waste disposal or the dealer where you purchased this product.
This information only applies to customers in the European Union, according to Directive 2002/96/EC of EU-
ROPEAN PARLIAMENT and THE COUNCIL OF 27January 2003 on waste electrical and electronic equipment (WEEE) and
legislation transposing and implementing it info the various notional legal systems. For other countries, please contact your local
government to investigate the possibility of recycling your product.