6/12
• Mounting on the wall
3.6 Accessibility of the connection points
Refer to annexe 4 for mounting and demounting of the SILENSYS
®
’ door.
3.7 Refrigeration connections
In order to always ensure the highest quality for our products, the refrigeration circuit of the
unit is supplied dry and filled with nitrogen.
ADVICES
To maintain the quality of a TECUMSEH EUROPE S.A. unit and to ensure its smooth operation it
is recommended to:
- Braze under nitrogen,
- Insulate the suction line up to the compressor inlet to avoid condensation.
Re. annexe 5 for the refrigeration connection.
To reduce the superheat on the suction side, the suction piping must be insulated. For low
temperature applications, use 19mm thick insulation.
3.8 Electrical connections
Advices
Access hatch
Safety latch