Temperzone UC8 Operation, OSA models with inverter, issue 1
Low pressure transducer fault
Transducer cable disconnected
Faulty transducer
Loss of refrigerant (gas leak)
High pressure transducer fault
Transducer cable disconnected
Faulty transducer
Loss of refrigerant (gas leak)
Suction line temperature sensor fault
Sensor cable disconnected
Discharge line temperature sensor fault
Sensor cable disconnected
Indoor coil temperature sensor fault
Sensor cable disconnected
Heating element temperature sensor fault
Sensor cable disconnected
Loss of serial communications
Loss of serial communications
Invalid DIP switches setting
Inadequate electrical box ventilation
Supply voltage out of bounds
Electrical short circuit / overload
High discharge superheat protection
Loss of refrigerant (gas leak)
Faulty transducer
EEV malfunctioning or disconnected
Pressure transducer connections
swapped
Incorrect pressure transducer fitted
EEV malfunctioning or disconnected
Reverse cycle valve fault
Reverse cycle valve disconnected
Invalid DIP switch setting on TZT-100
thermostat
Set TZT-100 DIP switch 2 ON
and TZT-100 DIP switch 4 OFF
Variable speed compressor driver reports a
fault
Evaporating temperature too high
Supply water temperature too high
(heating mode)
EEV malfunctioning or disconnected
Condensing temperature too low
Supply water temperature too low
(cooling mode)
EEV malfunctioning or disconnected
Invalid EEV mode selection