Do you have a question about the Tense DT-96 and is the answer not in the manual?
Brand | Tense |
---|---|
Model | DT-96 |
Category | Controller |
Language | English |
Selectable sensor input types including T/C and Pt100.
Selectable heating or cooling control mode for the device.
Configuration of hysteresis for heating and alarm functions.
Sets the proportional band width in degrees Celsius.
Defines the control loop cycle time in seconds.
Configuration of integral (Ti) and derivative (Td) times for PID control.
Setting upper (UP.L) and lower (Lo.L) limits for alarms.
Allows direct addition of an offset value to the measured value.
Choice of alarm modes: absolute, relative, or band.
Sets the value for relative or band alarm modes.
Minimum delay before OUT turns ON in cooling mode.
Determines OUT behavior when a 'Fail' message is displayed.
Setting the target temperature (Process SET) for heating.
Setting absolute alarm limits, displayed if Ab.AL=Yes.
Defines the logic for different alarm output types (Abs, Rel, Bnd).
ON-OFF control is active when 'H.Hys' is set to a value other than 0.
Details on PID, Proportional Band (PbC), Integral (Ti), and Derivative (Td) times.