Operating Instructions and Parts Manual
12 Terex T25I and T45I Super Quiet Generator
June 2006
REV A
THE WHEELS MUST BE PROPERLY CHOCKED
IF THE GENERATOR IS ON UNLEVEL
GROUND. DO NOT OPERATE THE GENERA-
TOR SET UNTIL IT HAS BEEN PROPERLY SE-
CURED.
When preparing to start the generator set, follow
the sequence listed below:
Check the coolant level in the radiator, and add
as necessary. If adding coolant, use only a
50/50 mixture of antifreeze and water. Refer to
your engine manufacturer's maintenance
manual for specific antifreeze information.
NEVER REMOVE THE RADIATOR CAP WHILE
THE ENGINE IS RUNNING OR WHILE THE
ENGINE IS HOT.
Check the oil level in the engine crankcase, and
add as required.
USE CLASS API, CC OR CD GRADE ENGINE
OIL. REFER TO ISUZU ENGINE MANUAL FOR
VISCOSITY AND QUANTITY.
If the battery is not a maintenance free battery,
check the electrolyte level in the battery and
add distilled water if necessary.
Check fuel/water separator for water in the fuel
system. Drain water from separator if
necessary.
Check fuel level in the fuel tank and add as
required. Check to insure the fuel tank vent is
“open” and not clogged.
If the axle is sloped downhill, turn the generator
set so that the axle is level.
Chock wheels if generator set is not on level
ground.
Unhook hitch, safety chains and running lights.
Rotate the tongue jack into position (90
degrees), release the hitch pin and raise the
tongue off the towing vehicle.
Level the generator set with the tongue jack.
USE #2 DIESEL FUEL ONLY.
Verify that the generator main circuit breaker is
in the “OFF” position.
Make sure the generator set is properly
grounded. This is accomplished by connecting
the grounding lug provided at the rear of the
generator set enclosure to a mechanical
earthground with a minimum 2/0 size #4 bare
electrical cable. If this differs from your local
code, always follow the local code for
grounding.
THIS GENERATOR SET PRODUCES VOLT-
AGES THAT CAN CAUSE SEVERE SHOCK OR
DEATH! ONLY QUALIFIED ELECTRICIANS
SHOULD PERFORM ELECTRICAL WORK.