25
A08 ON MAINTENANCE Alarm Maintenance by-pass switch on
A09 MANUAL BYPASS Alarm Load is transferred to by-pass from front panel
A10 BATTERY LOW SHUT Alarm Inverter measured battery voltage is low (shutdown level)
A11 REPO STOP Alarm External REPO input signal sensed
A12 DC BALANCE BAD Alarm Before inverter start fitler capacitors dont discharged
A13 PEAK CURRENT Alarm Very high current at the UPS output
A14 INV NOT START Alarm Inverter module start failed
A17 BYPASS FAILURE Warning
By-pass input voltage failure
A18 BYPASS VOLT Warning
By-pass input voltage out of tolerance
A19 BYP FREQ.TOLER Warning
By-pass input frequency out og tolerance
A20 OVERLOAD Warning
Currently the load exceeded 100% capacity
A21 OVERTEMP Warning
Currently inverter power modul heatsink temperature is high
A22 OUTPUT OFF Warning
There is no UPS output voltage
A23 ON BYPASS Warning
Load is on bypass
A24 REVERSE CURRENT Warning
Regenerative backfeed to UPS output
A25 INV RESET Warning
Inverter module power on
A26 BATTERY LOW Warning
Batteries are going to full discharge
A27 GENERATOR MODE Warning
Generator set is running
A28 O/P PHASE LOSS Warning
Anyone of the UPS output phases there is no voltage
A29 SYNCHRON BAD Warning
Inverter is not synchron to by-pass input
A30 SHORT CIRCUIT Warning
Short circuit occured at the UPS output currenty normal
A31 OUTPUT SWITCH Warning
Output switch of the UPS is off
A32 SERVICE LOGIN Warning
Service login active
A34 BYP ROTATE PHASE Warning
By-pass phase sequency incorrect
A35 INV STOP Warning
Inverter module interrupted
A36 INV DC DOWN Warning
DC BUS voltage is less then 120 volts DC
A37 AC CURR LIMIT Warning
Inverter output current limited
A38 FUSE FAILURE Warning
Any fuse in UPS is blowned
A39 PSP FAILURE Alarm Inverter control board power supply out of tolerant
A40 INVERTER START Warning
Inverter is in soft start stage wait for finish
A43 USER LOGIN Warning
User logged in to UPS
A45 SERV.PASSWORD Fault For UPS startup service password required
If any alarm shown on the LCD panel without A00 and R00 message UPS will start automatically if the
conditions are normal. But if you see A00 or R00 code with any alarm together you must CALL SERVICE !
If the message is warning UPS continues to run there is no problem.
To support technical service status cods are used, each status code tells different event to us.