(CC_f021)
Unable to charge - No primary Wall
Connector
Check that primary unit is powered
and available
What this alert means:
Circuit Breaker Sharing Network: Need one (and only
one) Wall Connector set to Master.
What to do:
Only one Wall Connector can be set to a master
configuration. All other linked Wall Connectors must be
set to paired (position F). Set one of the Wall
Connectors to Master and all others to paired.
(CC_f022)
Unable to charge - More than 1
primary unit
Ensure only 1 Wall Connector is set
as primary
What this alert means:
Circuit Breaker Sharing Network: Need one (and only
one) Wall Connector set to Master.
What to do:
Only one Wall Connector can be set to a master
configuration. All other linked Wall Connectors must be
set to paired (position F). Set one of the Wall
Connectors to Master and all others to paired.
(CC_f023)
Unable to charge - Too many Wall
Connectors
Ensure no more than 3 units paired
with primary
What this alert means:
Circuit Breaker Sharing Network: More than three Wall
Connectors are paired with the same Master.
What to do:
One or more paired Wall Connectors must be moved to
a dierent circuit and disconnected (unpaired) from this
Circuit Breaker Sharing Network.