1
TR 611 top2 24 V
6114100
TR 622 top2 24 V
6224100
307086
Time switch
EN
1. Basic safety information
Danger of death through electric shock or fire!
Installation should only be carried out by a
qualied electrician!
WARNING
The device is designed for installation on DIN top hat
rails (in accordance with EN 60715)
The device corresponds to type 1 STU in accordance with
IEC/EN 60730-2-7
Power reserve (10 years) is reduced if memory card is
inserted (using battery power)
!
OBELISK top2 memory card: Avoid mechanical overload
and contamination during storage/transportation
2. Proper use
The time switch is used for lighting, ventilation and
ushing applications etc.
Only for use in closed, dry rooms
!
Do not use on safety devices, e.g. escape route doors, re
safety equipment etc.
!
The external outputs are designed for operating voltage
of 12-24 V AC and DC and not for 230 V.
Disposal
Dispose of device in environmentally sound manner
3. Installation and connection
Mounting the time switch
Danger of death through electric shock or fire!
Installation should only be carried out by a
qualied electrician!
WARNING
click
45° cable
Plug-in screwless
terminal
OBELISK top2
memory card
(9070404)
Test tap
Load line connection
Mount on DIN top hat rails (as dened in EN 60715)
Switched voltage-free
Ensure device cannot be switched on
Check absence of voltage
Earth and bypass
Cover or shield any adjacent live components
Connecting the cable
Wiring diagrams 6114100 / 6224100
C1
123
12-24
V
+
~
~
Ext1
max. 100 m
+
~
~
C2
C1
123
456
Ext1
max. 100 m
max. 100 m
Ext2
12-24 V
+
~
~
+
~
~
Strip cable to 8 mm (max. 9)
Insert cable in the open DuoFix® plug-in terminal at 45°
L 2 cables per terminal position possible
To open the DuoFix® plug-in terminal, press screwdriver
downwards
!
TR 622: With these devices the type of low voltage must
correspond to low voltage type of the supply voltage
(SELV = SELV, PELV = PELV, FELV = FELV).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben TR 611 top2 and is the answer not in the manual?

Theben TR 611 top2 Specifications

General IconGeneral
TypeDigital timer
Voltage230 V AC
Number of Programs20
DisplayLCD
MountingDIN rail
Frequency50/60 Hz
Number of Channels1
Protection ClassIP20
Text-oriented ProgrammingYes
External InputNo
Automatic Summer/Winter Time ChangeoverYes
EEPROM Program BackupYes
Power230 V
Switching Capacity16 A
Time Range1 min to 168 h
Installation TypeDIN rail
Type of ContactChangeover contact
Timer Range1 min to 168 h