PRON NA60-MB0
Version 3.50
PRON NA60-MB0 Remote Setting Manual
Page: 25 of 59
VAR REF IDX DIM TYPE Range Um Kv ENUM
Thermal image - 49
Alarm DthAL1 1x 29 1 BIT 0=OFF, 1=ON
BLK1 DthAL1 1x 30 1 BIT 0=OFF, 1=ON
BLK2IN DthAL1 1x 31 1 BIT 0=OFF, 1=ON
BLK4IN DthAL1 1x 32 1 BIT 0=OFF, 1=ON
Alarm DthAL2 1x 33 1 BIT 0=OFF, 1=ON
BLK1 DthAL2 1x 34 1 BIT 0=OFF, 1=ON
BLK2IN DthAL2 1x 35 1 BIT 0=OFF, 1=ON
BLK4IN DthAL2 1x 36 1 BIT 0=OFF, 1=ON
Trip Dth> 1x 37 1 BIT 0=OFF, 1=ON
BLK1 Dth> 1x 38 1 BIT 0=OFF, 1=ON
BLK2IN Dth> 1x 39 1 BIT 0=OFF, 1=ON
BLK4IN Dth> 1x 40 1 BIT 0=OFF, 1=ON
CLP Dth 1x 41 1 BIT 0=OFF, 1=ON
Phase overcurrent - 50/51
Start I> 1x 42 1 BIT 0=OFF, 1=ON
Trip I> 1x 43 1 BIT 0=OFF, 1=ON
BLK1 I> 1x 44 1 BIT 0=OFF, 1=ON
BLK2IN I> 1x 45 1 BIT 0=OFF, 1=ON
BLK4IN I> 1x 46 1 BIT 0=OFF, 1=ON
CLP I> 1x 47 1 BIT 0=OFF, 1=ON
Start I>> 1x 48 1 BIT 0=OFF, 1=ON
Trip I>> 1x 49 1 BIT 0=OFF, 1=ON
BLK1 I>> 1x 50 1 BIT 0=OFF, 1=ON
BLK2IN I>> 1x 51 1 BIT 0=OFF, 1=ON
BLK4IN I>> 1x 52 1 BIT 0=OFF, 1=ON
CLP I>> 1x 53 1 BIT 0=OFF, 1=ON
Start I>>> 1x 54 1 BIT 0=OFF, 1=ON
Trip I>>> 1x 55 1 BIT 0=OFF, 1=ON
BLK1 I>>> 1x 56 1 BIT 0=OFF, 1=ON
BLK2IN I>>> 1x 57 1 BIT 0=OFF, 1=ON
BLK4IN I>>> 1x 58 1 BIT 0=OFF, 1=ON
CLP I>>> 1x 59 1 BIT 0=OFF, 1=ON