EasyManua.ls Logo

Thytronic NA60-MB0 PRON Series - Page 30

Thytronic NA60-MB0 PRON Series
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PRON NA60-MB0
Version 3.50
PRON NA60-MB0 Remote Setting Manual
Page: 30 of 59
VAR REF IDX DIM TYPE Range Um Kv ENUM
PLC2 counters
Counter 1 3x 128 2 ULONG 1
Counter 2 3x 130 2 ULONG 1
Counter 3 3x 132 2 ULONG 1
Counter 4 3x 134 2 ULONG 1
Counter 5 3x 136 2 ULONG 1
Counter 6 3x 138 2 ULONG 1
Counter 7 3x 140 2 ULONG 1
Counter 8 3x 142 2 ULONG 1
Counter 9 3x 144 2 ULONG 1
Counter 10 3x 146 2 ULONG 1
Counter 11 3x 148 2 ULONG 1
Counter 12 3x 150 2 ULONG 1
Counter 13 3x 152 2 ULONG 1
Counter 14 3x 154 2 ULONG 1
Counter 15 3x 156 2 ULONG 1
Counter 16 3x 158 2 ULONG 1
Circuit Breaker supervision
CB-State 3x 160 1 WORD 0="Open",1="Closed",2="?"
52a 1x 154 1 BIT 0=OFF, 1=ON
52b 1x 155 1 BIT 0=OFF, 1=ON
CB fail 1x 156 1 BIT 0=OFF, 1=ON
Break time assigned relays state 1x 157 1 BIT 0=OFF, 1=ON
State N.Open 1x 158 1 BIT 0=OFF, 1=ON
State SumI 1x 159 1 BIT 0=OFF, 1=ON
SumIL1 3x 161 2 ULONG In 16000
SumIL2 3x 163 2 ULONG In 16000
SumIL3 3x 165 2 ULONG In 16000
State SumI^2t 1x 160 1 BIT 0=OFF, 1=ON
SumIL1^2t 3x 167 2 ULONG In^2s 250000
SumIL2^2t 3x 169 2 ULONG In^2s 250000
SumIL3^2t 3x 171 2 ULONG In^2s 250000
State tbreak 1x 161 1 BIT 0=OFF, 1=ON

Related product manuals