PRON NA60-MB0
Version 3.50
PRON NA60-MB0 Remote Setting Manual
Page: 34 of 59
VAR REF IDX DIM TYPE Range Um Kv ENUM
Directional phase overcurrent - 67
ParStIPD>cnt - Value 3x 240 1 WORD
ParTrIPD>cnt - Value 3x 241 1 WORD
ParBk1IPD>cnt - Value 3x 242 1 WORD
ParBk2IPD>cnt - Value 3x 243 1 WORD
ParStIPD>>cnt - Value 3x 244 1 WORD
ParTrIPD>>cnt - Value 3x 245 1 WORD
ParBk1IPD>>cnt - Value 3x 246 1 WORD
ParBk2IPD>>cnt - Value 3x 247 1 WORD
ParStIPD>>>cnt - Value 3x 248 1 WORD
ParTrIPD>>>cnt - Value 3x 249 1 WORD
ParBk1IPD>>>cnt - Value 3x 250 1 WORD
ParBk2IPD>>>cnt - Value 3x 251 1 WORD
ParStIPD>>>>cnt - Value 3x 252 1 WORD
ParTrIPD>>>>cnt - Value 3x 253 1 WORD
ParBk1IPD>>>>cnt - Value 3x 254 1 WORD
ParBk2IPD>>>>cnt - Value 3x 255 1 WORD