VAR REF IDX DIM TYPE Range Um Kv ENUM
Energy measures
EA+ - Value 3x 451 2 LONG kWh 1
EA- - Value 3x 453 2 LONG kWh 1
EA - Value 3x 455 2 LONG kWh 1
EQ+ - Value 3x 457 2 LONG kvarh 1
EQ- - Value 3x 459 2 LONG kvarh 1
EQ - Value 3x 461 2 LONG kvarh 1
PT100 Probes
PT1 3x 463 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T1 3x 464 2 LONG ^C 10
PT2 3x 466 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T2 3x 467 2 LONG ^C 10
PT3 3x 469 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T3 3x 470 2 LONG ^C 10
PT4 3x 472 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T4 3x 473 2 LONG ^C 10
PT5 3x 475 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T5 3x 476 2 LONG ^C 10
PT6 3x 478 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T6 3x 479 2 LONG ^C 10
PT7 3x 481 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T7 3x 482 2 LONG ^C 10
PT8 3x 484 1 WORD 0="ON",1="WAIT",2="LOW",3
="HIGH",4="FAIL"
T8 3x 485 2 LONG ^C 10