SSG
11
SSG000\08
12-2005
I
θ
>,
I
θ
>>,
I
θ
>>> Soglie d'intervento relative alle funzioni
direzionali di massima corrente a tempo indipendente.
t
θ
>,
t
θ
>>,
t
θ
>>> Tempi d'intervento relativi alle funzioni
direzionali di massima corrente a tempo indipendente.
t
θ
>>
B
,
t
θ
>>>
B
Tempi d'intervento relativi alle funzioni
direzionali di massima corrente, attivati in sostituzione di
t
θ
>> o
t
θ
>>> quando la relativa funzione è predisposta con il
blocco in entrata.
I
S
,
I
θS
Correnti asintotiche di riferimento per la
determinazione dei tempi d'intervento delle funzioni di mas-
sima corrente a tempo dipendente.
I
T
,
I
θT
Soglie d'intervento relative alle funzioni
di massima corrente a tempo dipendente.
t
S
,
t
θS
Tempo di riferimento per le funzioni di
massima corrente a tempo dipendente, corrispondente al
tempo d'intervento relativo a un valore di corrente pari a 4
I
S
(o 4
I
θS
).
θ Angolo caratteristico per le funzioni dire-
zionali di massima corrente
(1)
.
I
E
>,
I
E
>>,
I
E
>>> Soglie d'intervento relative alle funzioni
non direzionali di massima corrente residua a tempo indi-
pendente.
t
E
>,
t
E
>>,
t
E
>>> Tempi d'intervento relativi alle funzioni
non direzionali di massima corrente residua a tempo indi-
pendente.
t
E
>>
B
,
t
E
>>>
B
Tempi d'intervento relativi alle funzioni
non direzionali di massima corrente residua, attivati in
sostituzione di
t
E
>> o
t
E
>>> quando la relativa funzione è
predisposta con il blocco in entrata.
I
ES
Corrente asintotica di riferimento per la
determinazione del tempo d'intervento della funzione di
massima corrente residua a tempo dipendente.
I
ET
Soglia d'intervento relativa alla funzione
di massima corrente residua a tempo dipendente.
t
ES
Tempo di riferimento per la funzione di
massima corrente residua a tempo dipendente, corrispon-
dente al tempo d'intervento relativo a un valore di corrente
pari a 4
I
ES
.
U
E
>,
U
E
>> Soglie d'intervento relative alla funzione
di massima tensione residua.
t
UE
>,
t
UE
>> Tempi d'intervento relativi alle funzioni di
massima tensione residua a tempo indipendente.
I
ED
>,
I
ED
>>,
I
ED
>>> Soglie d'intervento di massima corrente
residua relative alle funzioni direzionali di guasto a terra a
tempo indipendente
(2)
.
U
ED
>,
U
ED
>>,
U
ED
>>> Soglie d'intervento di massima tensione
residua relative alle funzioni direzionali di guasto a terra
(2)
.
θ
E
>, θ
E
>>, θ
E
>>> Angolo caratteristico per le funzioni dire-
zionali di guasto a terra
(3)
.
β>, β>>, β>>> Massima deviazione dell'angolo caratte-
ristico relativa alle funzioni direzionali di guasto a terra
(3)
.
I
θ
>,
I
θ
>>,
I
θ
>>> Operation threshold values concerning
the independent time directional overcurrent protection
functions.
t
θ
>,
t
θ
>>,
t
θ
>>> Operation time values concerning the
independent time directional overcurrent protection functions.
t
θ
>>
B
,
t
θ
>>>
B
Operation time values concerning the
directional overcurrent protection functions, which are
activated in place of
t
θ
>> or
t
θ
>>> when the corresponding
function is preset with input blocking.
I
S
,
I
θS
Asymptotic reference currents for the de-
termination of the operation times for dependent time
overcurrent functions.
I
T
,
I
θT
Operation threshold values concerning
the dependent time overcurrent functions.
t
S
,
t
θS
Reference time concerning the dependent
time overcurrent functions, represented by the operation time
corresponding to a current value equal to 4
I
S
(or 4
I
θS
).
θ Characteristic angle for directional
overcurrent protection functions
(1)
.
I
E
>,
I
E
>>,
I
E
>>> Operation threshold values for independ-
ent time non-directional residual current protection functions.
t
E
>,
t
E
>>,
t
E
>>> Operation time values concerning the in-
dependent time non-directional residual overcurrent pro-
tection functions.
t
E
>>
B
,
t
E
>>>
B
Operation time values concerning the
non-directional residual current functions, which are
activated in place of
t
E
>> or
t
E
>>> when the corresponding
function is preset with input blocking.
I
ES
Asymptotic reference current for the de-
termination of the operation time for dependent time residual
current function.
I
ET
Operation threshold value for the depend-
ent time residual current function.
t
ES
Reference time concerning the dependent
time residual overcurrent function, represented by the opera-
tion time corresponding to a current value equal to 4
I
ES
.
U
E
>,
U
E
>> Operation threshold values for the re-
sidual voltage protection function.
t
UE
>,
t
UE
>> Operation time values concerning the independent
time residual overvoltage functions.
I
ED
>,
I
ED
>>,
I
ED
>>> Operation threshold values for the residual
current, relating to the independent time directional earth
fault protection functions
(2)
.
U
ED
>,
U
ED
>>,
U
ED
>>> Operation threshold values for the residual
voltage, relating to the directional earth fault protection
functions
(2)
.
θ
E
>, θ
E
>>, θ
E
>>> Characteristic angle for directional
residual current protection functions
(3)
.
β>, β>>, β>>> Maximum deviation from the characteris-
tic angle, relating to the earth fault protection functions
(3)
.
NOTA 1 - Le funzioni direzionali di massima corrente di fase si basano, per ciascuna
delle tre fasi, sul valore di corrente
I
θ
=
I
· cos(ϕ - θ)
in cuiϕ rappresenta lo sfasamento in ritardo del fasore di corrente rispetto al
corrispondente fasore di tensione (tensione fase-neutro).
NOTA 2 - La prima funzione direzionale di guasto a terra interviene al verificarsi
congiunto delle seguenti tre condizioni:
- la corrente residua superi la relativa soglia
I
ED
>,
- la tensione residua superi la relativa soglia
U
ED
>,
- lo sfasamento j
E
sia compreso tra (θ
E
> - β>) e (θ
E
> - β>).
Per le altre due funzioni direzionali di guasto a terra sussistono condizioni analo-
ghe.
NOTA 3 - Il significato dei parametri θ
E
e β è illustrato nel diagramma di fig. 11.
NOTE 1 - The overcurrent directional functions are based, for each one of the three
phase currents, upon the following current value
I
θ
=
I
· cos(ϕ - θ)
where ϕ represents the lag phase shift of the current phasor with respect to the
corresponding voltage phasor (phase to neutral voltage).
NOTE 2 - The first directional earth fault function operates upon the occurrence of all
the following three conditions:
- the residual current exceeds its corresponding threshold
I
ED
>,
- the residual voltage exceeds its corresponding threshold
U
ED
>,
- the phase shift ϕ
E
is between (θ
E
> - β>) and (θ
E
> + β>).
For the other two directional earth fault functios thecorresponding similar conditions
apply.
NOTE 3 - The meaning of parameters θ
E
and β is explained on the drawing of fig. 11.