E. VFD Status Verification
Determine which of the LEDs on the Status Panel, located below the red Display LED on the VFD, is lit.
If FREF is lit, continue on to record the status of Run and Alarm LEDs.
If an LED other than the FREF LED is lit, press the DSPL button until the FREF LED becomes
lit.
Indicate the status of the following LEDs located on the VFD by checking the appropriate box within the following table.
IMPOR
TANT
If ANY of your indications fall within a shaded box, continue on to Section X-3 on page 11 and locate the corre-
sponding solution.
If NONE of your indications fall within a shaded box, continue.
F. Transducer Set-Up Verification
Verify that the sensing tube is connected to the Transducer Port closest to you and furthest from the surface upon
which the transducer is mounted.
3
VFD
IMPORTANT CPC-3 INDICATORS
LIT
UNLIT
BLINKING
Run LED
Alarm LED