What to do if my TLV COSR-16 Control Unit is hunting or chattering?
- VVincent WaltersAug 16, 2025
If your TLV Control Unit is hunting or chattering, consider these potential causes and solutions: * The unit might be operating below the lower flow rate limit. Check the volume of steam supply and replace with a smaller diameter valve. * There might be too high a reduction ratio (operated at below 10% of the primary pressure). Use a two-stage reduction arrangement. * The selected model may be inappropriate for the service conditions. Check the model selection and replace the COSR if necessary. * Condensate is contained, or the trap is blocked. Check the trap and the piping.


