TOPVERT G1/H1/P1 Series
E-16
FUNCTIONS AND PARAMETER SUMMARY
=This parameter cannot be set
during operation.
: Available in Firmware Version
2.xx and after only.
: Available in Firmware Version
3.xx and after only.
{ }Parameter no. in
Firmware Version 1.xx
[ ] :optional
Group 0: System parameters
Parame
ters
Functions Settings
Factory
Setting
User
Pr0-00
Model display Display according to the model number
Read
Only
Pr0-01
Rated output current to
motor
Display according to the model number
Read
Only
Pr0-02
Parameter Reset (Motor
V/F selecting)
10: Parameter reset for 60Hz - 230/460/575V motor
application
8
9: Parameter reset for 50Hz - 220/380/575V motor
application
8: Parameter reset for 60Hz - 220/380/575V motor
application
7: Parameter reset for 50Hz - 230/460/575V motor
application
6: Parameter reset for 60Hz - 240/415/575V motor
application
5: Parameter reset for 50Hz - 240/415/575V motor
application
Pr0-03
Password Input (The Key)
0
9999
0
Pr0-04
Password set (The Lock)
0
9999
0
Pr0-05
Parameter Locking Level
Bit0
(bxxxx0)
0
All parameters are readable,
b00000
1
Parameters after Pr0-05 cannot
read ”Err” message will displayed
when try to read.
Bit1
(bxxx0x)
0
Enable Frequency Command.
1
Disable frequency command
Bit2
(bxxx0x)
0
Enable run command from PU
1
Disable run command from PU
Pr0-06
Power on display
selection
0: Frequency command value
0
1: Actual output frequency (Hz
2: Output current
3: User defined contents on Pr0-07
Pr0-07
Versatile display
0: Motor speed (RPM)
0
1: DC-Bus Voltage (Vdc)
2: Actual output voltage (Vac)
3: Output voltage command value (Vac)
4: PID feedback frequency value (Hz)
5: Running step no. of MSS run
6: Sleep time (Pr8-07)
7: Auto-Restart after Fault (Pr6-10)
8: PID frequency command value (Hz)
9: (Factory Reserved)
10: Output power factor angle ( º )
11: Counter value
12: Over-Torque detection time 1 (Pr5-17)
13: (Factory Reserved)
14: Dwell Time at Accel. (Pr6-14)
15: Dwell Time at Decel. (Pr6-16)
16: DC Braking time in Start-up (Pr6-01)
17: DC Braking Time during stop (Pr6-02)
18: Remain time of the executing MSS Run
19: (Factory Reserved)
20: (Factory Reserved)