ENGLISH ( EN )
24
8. TECHNICAL SPECIFICATIONS
*HEIGHTxWIDTHxDEPTH
Supply Voltage 230 V AC or 400 V AC (depending on model) / -20%...+30% /
50/60Hz
Motor current range 0,5…..18 A / AC3
Protections Underload, overload, phase failure and over-voltage
Level control Two probes, timed probe, no probes or ow switch
Inhibition time (ow detector) Selectable in 15, 30, 60, or 90 seconds
Underload setting OFF - 0,5… 21 A (jump in 4 seconds)
Overload setting 0,5…21 A (jump in 7 seconds)
Restart time Disabled (OFF) or adjustable from 3 minutes up to 8 hours
Control voltage (probes/oats) 12 V AC
External control (EXT. ON/OFF) Dry contact or voltage from 6 to 24 V AC/DC
Terminal blocks wiring size 10 mm² (power) / 4 mm² (control)
Cable glands Supply and Pump: 2xM20 / Control: 2xM16
Recording information
(PUMPCHECK)
Module identication number, pump running hours, pump
starts, pump alarms and last alarm trip current
Size*/Weight/IP/Temperature 240 x 190 x 110 mm / 1,82 kg / IP65 / -10…+55 ºC