8-6-2. Outdoor unit
No. Component name Check procedure
1
Compressor
Type
DX150A1T-21F
(401HW-E, 601HW-E)
NX220A1FJ-20N
(801HW-E, 1101HW-E)
Measure the resistance value of each winding with a tester.
2
Outdoor fan motor
Type
ICF-140-A43-1
(401HW-E, 601HW-E)
ICF-280-A60-1
(801HW-E, 1101HW-E)
Measure the resistance value of each winding with a tester.
3
4-way valve coil
Type
DXQ-1233
Measure the resistance value.
9 ± 0.9 Ω
401HW-E, 601HW-E
Location
Resistance
value
Red
− White 1.04 - 1.16 Ω
White
− Black 1.04 - 1.16 Ω
Black
− Red 1.04 - 1.16 Ω At 20°C
801HW-E, 1101HW-E
Location
Resistance
value
Red
− White 1.16 - 1.28 Ω
White
− Black 1.16 - 1.28 Ω
Black
− Red 1.16 - 1.28 Ω At 20°C
401HW-E, 601HW-E
801HW-E, 1101HW-E
Location Resistance value
Red
− White
21.00 ± 1.05 ΩWhite
− Black
Black
− Red
Location Resistance value
Red
− White
32.6 ± 3.3 ΩWhite
− Black
Black
− Red