Model name:
Outdoor unit
HWT-401HW-E(TR)
HWT-601HW-E(TR)
HWT-801HW-E(TR)
HWT-1101HW-E(TR)
HWT-801HRW-E
HWT-1101HRW-E
AIR TO WATER HEAT PUMP
Hydro unit
-Wall Mounted Type-
HWT-601XWHM3W-E(TR)
HWT-601XWHT6W-E(TR)
HWT-1101XWHM3W-E(TR)
HWT-1101XWHT6W-E(TR)
HWT-1101XWHT9W-E(TR)
Service Manual
FILE No. AE0-2101W

Table of Contents

Other manuals for Toshiba HWT-601XWHT6W-E

Questions and Answers

  • V
    vmendozaAug 10, 2025
    What to do if my Toshiba Heat Pump room is not heated or cooled properly?
    • A
      Alexander JeffersonAug 10, 2025
      If your Toshiba Heat Pump isn't heating or cooling the room adequately, or the water isn't hot enough, there might be several reasons: * The remote controller settings may be incorrect. Check the operation and temperature settings. * The function code setting could be wrong. Verify it using the function code table. * The backup heater might be disconnected. Inspect the backup heater and bimetal thermostat. * The unit might have insufficient capacity. Review the equipment selection. * A temperature sensor may be defective or not properly positioned. Ensure the temperature sensor is correctly installed.
  • R
    Robert EstradaAug 15, 2025
    What to do if nothing is displayed on the Toshiba HWT-601XWHT6W-E Heat Pump remote controller?
    • J
      Justin RossAug 15, 2025
      If nothing is displayed on your Toshiba Heat Pump's remote controller, check the following: * Verify the power supply wiring. * Check the setting with the DN codes.
  • J
    Jennifer AcevedoAug 20, 2025
    What to do if my Toshiba HWT-601XWHT6W-E has almost no or little water flow and shows error code [A01]?
    • C
      Cindy MorrisAug 21, 2025
      If your Toshiba Heat Pump exhibits little to no water flow and displays error code [A01], consider the following: * There may be an air bite in the pump. Release the air completely, following the correct procedure. * The hydraulic pressure may be low. Set the hydraulic pressure appropriately, considering the pipe height, and replenish water until the manometer shows the set hydraulic pressure or more. * The strainer might be clogged. Clean the strainer. * There could be large resistance on the hydro side. Widen the water path to the Hydro Unit or adopt a bypass valve. * The motorized 3-way valve for hot water supply might be malfunctioning. Check the wiring and parts.
  • B
    barbara42Aug 28, 2025
    Why is hot water leaking from the overpressure preventive valve of my Toshiba HWT-601XWHT6W-E?
    • J
      Jonathan MooreAug 28, 2025
      Hot water leaking from the overpressure preventive valve of your Toshiba Heat Pump can be due to: * Excessive hydraulic pressure. Set the hydraulic pressure considering pipe height and replenish water until the manometer shows a value of set hydraulic pressure or more. * Insufficient capacity of the expansion tank. Check the expansion tank capacity compared to the total water amount; if it's insufficient, install another expansion tank. * Expansion tank failure. Check the air pressure.
  • C
    Cory MathisSep 2, 2025
    How to fix a Toshiba Heat Pump pump lock with error code [A14]?
    • C
      Crystal SandersSep 2, 2025
      If your Toshiba Heat Pump's pump is locked and displays error code [A14], it may be due to pump lock caused by dust clogging. To unlock it, insert a Phillips screwdriver into the hole and turn it to the left or right.

Summary

Definition of qualified installer or qualified service person

Refrigerant R32

Safety caution concerned to refrigerant R32

Safety precautions related to R32 refrigerant pressure and handling during installation/service.

Safety and cautions on installation; service

Detailed safety guidelines and precautions for installation and servicing of R32 refrigerant systems.

Specifications

Refrigeration cycle; Water system diagram

Wiring diagram

Key electric component rating

Method of defect diagnosis

Matters to be confirmed first

Initial checks for power supply, wiring, and sensor installation before diagnosing defects.

How to diagnose by error code

Provides detailed flow charts for diagnosing specific error codes detected by the Hydro Unit.

Defect mode detected by the outdoor unit

TD sensor error

Troubleshooting steps for TD sensor errors, including resistance and connection checks.

TE sensor error

Troubleshooting steps for TE sensor errors, including resistance and connection checks.

TS sensor error

Troubleshooting steps for TS sensor errors, including resistance and connection checks.

PD sensor error

Troubleshooting steps for PD sensor errors, including value checks and connection verification.

Defect mode detected by the remote controller

Not displaying at all (cannot operate by the remote controller)

Troubleshooting for cases where the remote controller displays nothing or cannot operate the unit.

E01 No communication between hydro unit and remote controller

Steps to diagnose and resolve communication errors between the hydro unit and remote controller.

Operation check by PC board switch

Hydro unit and outdoor unit settings

Hydro unit Setting

Lists Hydro unit DN codes, their descriptions, default values, and factory defaults for settings.

Test run

Scheduled Operation Setting

How to set scheduled operation

Guides on setting up scheduled operations, including condition and holiday settings.

Frost protection Setting

NIGHT Operation Setting

Anti bacteria Setting

Hot water boost Setting

Night time Low-noise Setting

Display Function of Set Temperature and Other Settings

Periodic inspection items

Hydro unit

Lists periodic inspection details for the Hydro unit, including insulation and operation checks.

Outdoor unit

Lists periodic inspection details for the Outdoor unit, covering insulation, power source, and fan.

Toshiba HWT-601XWHT6W-E Specifications

General IconGeneral
ModelHWT-601XWHT6W-E
CategoryHeat Pump
RefrigerantR32
Cooling Capacity6 kW
Heating Capacity6 kW
Noise Level (Outdoor)50 dB