4
Pulse motor valve coil
Type
PQ-M10012-000313
(401HW-E, 601HW-E)
UKV-A040
FAM-MD12TF-1
(801HW-E, 1101HW-E)
PQ-M10012-000313
UKV-A040
FAM-MD12TF-1
5
2-way valve coil
Type
TEV-SMOAJ2170A1
(801HW-E, 1101HW-E)
Measure the resistance value.
2163 ± 151
6
Suction temperature (TS) sensor
Heat exchange temperature
(TE) sensor
Outdoor temperature (TO)
sensor
Remove the connector and measure the resistance value with a tester.
10-20 k (Normal temperature)
7
Discharge temperature (TD)
sensor
Heat exchanger coil temperature
(TL) sensor
Remove the connector and measure the resistance value with a tester.
No. Component name Check procedure
M
1 White
5 Red
3 Orange
Yellow
2
Gray
6
Blue
4
Location Resistance value
Red White, Orange
46 ± 3.7
Gray Yellow, Blue
M
1 Black
6 Gray
3 Red
Yellow
2
Gray
6
Orange
4
Location Resistance value
Gray
Black, Red
46 ± 3
Gray
Yellow, Orange
M
1 White
6 Red
3 Orange
Yellow
2
Red
6
Blue
4
Location Resistance value
Red White, Orange
46 ± 4
Red
Yellow, Blue
Temperature
0°C 10°C 20°C 30°C
Sensor (kΩ)
Suction temperature (TS) sensor
33.8 20.4 12.6 8.0Heat exchange temperature (TE) sensor
Outdoor temperature (TO) sensor
Temperature
0°C 10°C 20°C 30°C
Sensor (k)
Discharge temperature (TD) sensor
161.3 99.0 62.4 40.2
Heat exchanger coil temperature (TL) sensor